Tugas Akhir
Analysis of kvar import anomaly in main transformer no. 2 of plta siman and alternative solutions to improve operational efficiency / MOHAMAD FAREL FIRMANSYAH
Abstrak
PLTA Siman experienced a technical issue involving reactive power import (negative kVar) in Main Transformer No. 2 which operates in parallel with two other transformers. This anomaly is caused by mismatched voltage ratios and impedance values between transformers resulting in circulating currents and the absorption of reactive power back into the transformer. This condition increases system losses and leads to additional costs due to PLN s reactive power tariff policy. This study aims to identify the root cause design alternative technical solutions and analyze the effectiveness of each solution in reducing kVar import. Three scenarios were tested through system simulation using ETAP software installation of a 569.9 kVar capacitor bank implementation of a Standard Operating Procedure (SOP) for PMT disconnection during standby and transformer replacement. The simulation results show that the SOP solution reduced kVar import by up to 100% during standby the capacitor bank reduced it by approximately 70% and transformer replacement eliminated circulating current entirely. Therefore the combination of SOP implementation and capacitor bank installation provides an optimal technical approach without requiring major intervention in main equipment.