Tugas Akhir
Power factor improvement analysis on the existing station service transformer at wlingi hydroelectric power plant using an lc filter compensator / RUTH NIKE DAUHAN
Abstrak
This research aims to improve power quality in the auxiliary system (PS) of PLTA Wlingi by correcting the power factor and mitigating harmonics. Based on simulation of the existing condition the system had a low power factor of 0.49 and harmonic levels close to the standard limit. The implemented solution involved installing a 317.66 kVar capacitor bank and adding a tuned passive L-C filter at the 9th harmonic order. Simulation results show an improved power factor of 0.83 and a reduced voltage THD of 2.21%. This strategy proved effective in enhancing system efficiency and complying with the IEEE Std 519 power quality standard.